window.dataLayer = window.dataLayer || []; function gtag(){dataLayer.push(arguments);} gtag('js', new Date()); gtag('config', 'G-ZJMPYD9EC7');

Nano 2 Relay Tree

$135.00

Item no.: 100395

The Loxone Nano 2 Relay Tree is your solution to quickly and easily integrate shades, lights, fans, pumps and other actuators using Loxone Tree technology. The flush-mounted piece offers two digital outputs including automatic end position detection.

  • 2 digital outputs (dry contact, shared hot)
    – relays rated for 10A (max 250V)
    – total load max 12A
  • Fully automatic control of shading, lights, fans, pumps, etc..
  • Fully automatic end position detection
  • Ready to use in record time thanks to Loxone Tree technology
  • Compact design: 42 x 39 x 20.5 mm / 1.7 x 1.5 x 0.8 in
  • ETL Listed

Complete flexibility and versatility for all switching tasks

The two digital outputs enable the integration of all types of shading and even decentralized switching of lights, blinds, fans, pumps, etc.

This means you can avoid needing to run your switch circuit back to your panel – reducing cabling and installation time.

With shading, for example – whether you use electronic roller shutters, blinds, curtains or
awnings – the new flush-mounted Nano 2 Relay Tree can be easily integrated in just a few steps to start automatically lowering or raising your shades.

The digital outputs are volt-free and can handle up to 250VAC. Please note that LED lighting can present high currents.

Fully automatic shading with end position detection


The Nano 2 Relay Tree can automatically detect the end position of your shading.

The current position of the shading will be instantly and reliably displayed right in the Loxone App.

100% designed for Loxone integration

This new product works 100% with the rest of your Loxone components. Thanks to the full integration using Loxone Auto Config, the following functions are standard from day one:

  • Loxone Switch Standard
  • Frost protection
  • Storm protection
  • Central control
  • Automatic shading

Loxone Tree: ready in record time


The Nano 2 Relay Tree, like all other Tree products, are “plug & play” and work seamlessly with all other Loxone products. It takes just minutes to install thanks to flexible cabling.

Quick & easy installation

Compact design and long (150 mm) connection cables make it easy to install the Nano 2 Relay Tree.

1. Power supply

We recommend the specially developed Tree cable for power supply and Tree communication.

2. Search and learn

In just a few moments, you can find and identify the Nano 2 Relay Tree in the Loxone Config.

3. Configure

Use the Loxone Auto Config to integrate the Nano 2 Relay Tree with all shading functions.

Electrical Data

  • Power Supply: 18 to 28VDC
  • Power consumption: typ. 0.1W, max. 0.34W
  • Output: 2 digital outputs (Relays), dry contact, shared hot max. 250VAC 10A at cosᵠ=1 (IEC) or max. 30VDC 10A, total load max. 12A
  • Power loss at max. load: 2.2W
  • Minimum load for automatic end stop detection: 100mA
  • Current detection setting range: 100 … 5000mA
  • Ambient temperature: -40 to 55°C / -40 to 131°F
  • Humidity: max. 95% r.H. (non condensing)

Downloads

Shipped in the Box

  • 1 x Nano 2 Relay Tree
  • 1 x Instructions

If using the Miniserver

Components List

    • 1 x Miniserver is required
    • 1 x Network Switch or Modem required
    • 1 x 24VDC Power supply required

Wire List

    • 1 x Cat5 or better, network Cable to connect the Miniserver to your network or computer to program the system
    • 1 x 18 AWG to 23 AWG pair (solid core preferred) to transfer power from Power supply to Miniserver
    • 1 x 18 AWG to 23 AWG pair (solid core preferred) to transfer power from the Power supply or Miniserver to the Tree device
    • 1 x 18 AWG to 23 AWG twisted pair (solid core and shielded preferable) to connect the Miniserver’s Tree Link to the Tree device

If using the Miniserver Go

Components List

Wire List

    • 1 x Cat5 or better, network Cable to connect the Miniserver Go to your network or computer to program the system
    • 1 x 18AWG to 23 AWG wire (solid core preferred) to ground from Power supply negative to the Miniserver Go
    • 1 x 18 AWG to 23 AWG pair (solid core preferred) to transfer power from Power supply to Tree Extension
    • 1 x 18 AWG to 23 AWG pair (solid core and shielded preferable) to transfer power from the Power supply to Tree device
    • 1 x 18 AWG to 23 AWG twisted pair (solid core and shielded preferable) to connect the Miniserver Go’s Loxone Link to the Tree Extension
    • 1 x 18 AWG to 23 AWG twisted pair (solid core and shielded preferable) to connect the Tree Link from the Tree Extension to the Tree device

Connection Diagram